Smart environmental monitoring solutions

Talk to our sales team. Call +61 2 9622 6327

Request a quote
Back to products

HT41 & HT42

Temperature Controller with Limiter Function

  • Temperature controller for all JCT heated sample lines
  • For operation with elevated safety requirements due to limiter function
  • Also universally applicable
  • Also for the operation of explosion-proof heated sample lines in Ex-zone 2 applicable

Have questions? Call +61 2 9622 6327

BENEFITS

  • Long lifetime due to contactless switching
  • High switching capacity of 3680 W
  • Self programmable and free configurable
  • Pre-parameterised ex works on request
  • Robust compact design
  • Limiter function with permanent switch-off according to DIN/VDE 0721
  • Switch-off temperature adjustable (50°C….500°C)
  • Alarm relay for 6 A

 

FEATURES

  • PID-controller
  • Wall mounting housing IP 65
  • 4-digit LED-indication
  • Membrane keypad with 4 push buttons
  • Alarm outlet with limit compensation (±10°C to set point)
  • Controller oulet with triac
  • Freely programmable
  • Auto tuning
  • Temperature controller for all JCT heated sample lines
  • For operation with elevated safety requirements due to limiter function
  • Also universally applicable
  • Also for operation of explosion proof heated sample lines in Ex-zone 2 applicable

 

Model HT41HT42
Descriptiontemperature controller with limiter function
Order code
ConnectionsHANQ8-socket (8-pole+PE) and mains cablewith cable glands
CONSTRUCTION
Installationwall mounting, 4 x M4
Dimensions80 x 182 (211) × 60 mm
Mounting surface100 x 162 mm
Degree of protectionP 65 (EN 60529)
Protection classI
OperationFilm keypad, 4 push buttons
Housing materialMakrolon
ApprovalsCE
Dimensions over all (W x H x D)rear panel mounting: 277 x 307 x 360 mm side panel mounting: 403 x 307 x 234 mm
Installationstand alone or wall mounting
Mounting positionhorizontal
Weight17,5 kg18 kg
Housing / Colourstainless steel / natural
Dead volume per gas path67 ml2 x 50 ml
Connection sample gas inletPVDF and 1.4401: 6 mm tube; glass: GL14 with hose connection
Connection sample gas outlet and condensate outlet on top (standard)PVDF: PVDF hose fitting DN 4/6; 1.4401: 6 mm tube; glass: GL14 with hose connection
Connection condensate outlet at the bottom (on request)PVDF and 1.4401: 12 mm tube; glass (only Mono available): GL18 with hose connection
Protection classIP 20 (EN 60529 / EN 61010)
Approvals / SignsCE
ELECTRICS
Power supply230 VAC 50 Hz, optional 115 VAC 60 Hz
Noise immunityEN 50 082-2
Emitted interferenceEN 50 081-1
Sensor typesFe-CuNi (J), NiCr-Ni (K), with reference point compensation and sensor breakage safeguard,
sensor polarity reversal control PT 100, 2 conductors DIN/IEC
Fault limit0.1 % to 0.2 % of the range
Controller outletelectrical switch (control) 16 A. Triac
Alarm outletrelais 6 A, limit compensation Y3, ‡10K of rated value
Controller responsePID
Limiter functionsignal via 2. PT 100
Cutout temperature limiter50°C to 500°C adjustable, actuates via mechanical relay 16 A
Display current / rated value4-digit LED display (13 mm high)
Measuring range-199 to +999 digit
Deviation display7 LED +12°C flashing
Setting ex works*PT 100. 0°C to 200°C
Optionexternal set point input

“The customer can reprogram these parameters or settings are supplied as required (extra charge).”

DOWNLOADS